Find the generator wattage needed
Back to calculator ↑List only what runs together
A generator only needs to power what you switch on during an outage, not the whole house. Add up the running watts of everything used at the same time. In a Thai house, that's usually the fridge, fans, lights, the router and often the water pump, because a tank-and-pump system stops supplying water when the power goes. Use input watts from labels or a meter. Don't use aircon BTU, motor horsepower or "maximum" marketing figures.
Running watts and starting watts
Generators have two ratings. Running (continuous) watts is what they can supply for hours. Starting (surge) watts is a brief extra burst for motors starting up. Your load must fit both.
Starting estimate = total running watts + the largest extra start of any one appliance. "Extra" means the amount above that appliance's running watts. A pump that runs at 500 W and needs 1,700 W to start has 1,200 W extra. Don't enter 1,700 W, because that counts the 500 W twice. The calculator assumes motors start one at a time.
Worked example: the defaults
1,800 W running plus a largest extra start of 1,200 W gives a 3,000 W starting estimate. Sizing mode shows that you need at least 1,800 W running and 3,000 W starting.
In comparison mode, the default candidate generator is rated 3,000 W running and 4,000 W starting. That leaves 1,200 W of running headroom and 1,000 W of starting headroom, so both pass. If either headroom is negative, that rating is exceeded, even if the other one passes.
Quick reference: Thai house scenarios
| Scenario | Running W | Largest extra start W | Starting estimate |
|---|---|---|---|
| Essentials plus water pump 400 W | 760 | 800 (pump) | 1,560 W |
| Calculator default | 1,800 | 1,200 | 3,000 W |
| Essentials, pump and one 1,000 W inverter aircon* | 1,760 | 800 (pump) | 2,560 W |
*This only holds if the aircon's extra start is below the pump's 800 W. Ask the manufacturer, because start behaviour varies by model.
Treat these as minimums. Leave some margin, because generators lose capacity in heat and with age, and loads change.
Ratings in kVA, amps and outlets
Some Thai generators are sold in kVA. Ask for the rating in watts or kW, which can be lower. If an appliance label shows amps, volts × amps gives VA, which equals watts only for simple heating loads. Motors need the manufacturer's figure. Also check each outlet. A single socket on the generator may be rated well below the machine's total, so spread loads across outlets.
Safety: the part that matters most
Run the generator outdoors only, at least about 6 m from doors, windows and vents, with the exhaust pointing away. An open garage or carport against the house is not safe. Use a working carbon-monoxide alarm. Never plug a generator into a wall socket to power the house. This "back-feeding" can kill line workers and damage equipment. A house connection needs a transfer switch installed by a qualified electrician. Let the engine cool before refuelling, and store fuel safely. PEA describes a 230/400 V, 50 Hz system. Check that the generator output, your supply and appliance nameplates match.
Limits
The calculator doesn't check voltage, phase, frequency, power quality, surge duration, simultaneous motor starts, or derating for heat and altitude. If several motors may start together, or equipment is sensitive, have an electrician assess the actual load.
Common questions
What size generator do I need for a house in Thailand?
For fridge, fans, lights, router and a 400 W water pump, aim for at least 760 W running and 1,560 W starting, plus some margin. Measure your real loads and confirm the pump's start demand with its manufacturer.
Should I add every appliance's starting watts?
No. If motors start one at a time, only the largest extra start counts. If the pump and fridge could start at the same moment, add both extras or have the load assessed.
Can a portable generator run my aircon?
Possibly, if both ratings cover it. Essentials, a pump and one 1,000 W inverter aircon come to about 1,760 W running and 2,560 W starting in our example. Check the aircon's rated input and start behaviour.
My appliance shows amps, not watts. What do I enter?
For heaters and kettles, volts × amps gives about the watts. At 230 V, 2 A is about 460 W. For motors, use the manufacturer's running and starting figures, because power factor makes the simple sum unreliable.
What's the difference between kVA and watts?
kVA is apparent power. Watts are what your appliances use. Many generators supply fewer watts than their kVA figure, so ask for the watt rating before comparing.
Can I run the generator in the carport or garage?
No. Carbon monoxide can enter the house even with doors open. Run it outdoors, about 6 m from openings, with the exhaust pointing away.
If both ratings pass, is it safe to connect to the house?
No. Voltage, phase, protection and connection method need checking. A whole-house connection requires a transfer switch installed by a qualified electrician.